Back /
NV-12 Vacuum Circuit Breaker (6–10 kV)

NV-12 series vacuum circuit breakers are designed for operation in switchgear of three-phase AC networks with 50 Hz frequency and 6 or 10 kV rated voltage, with neutral isolated or earthed through an arc-suppression reactor or resistor.
Various designs allow installation in all types of switchgear cabinets (KRU) and single-side service cells (KSO), as well as replacement of outdated circuit breakers under retrofit programmes.
Features:
- Vacuum interrupter in each pole; spring-motor operating mechanism
- Withdrawable version: truck, 2×24 or 1×72-pin connectors, lamellar contacts, mechanical and electromagnetic interlocks
- Fixed version: for KSO and KRU cells, retrofit
- Control circuits: 220 V or 110 V
- Installation altitude up to 1000 m; mechanical stress group M40 (GOST 17516.1)
Technical data:
| Rated voltage | 6 / 10 kV (maximum operating — 12 kV) |
| Power-frequency test voltage (1 min, 50/60 Hz) | 42 kV |
| Lightning impulse test voltage | 75 kV |
| Rated current | 630 / 1250 / 1600 A |
| Rated breaking current | 20 / 25 / 31.5 / 40 kA |
| Short-time withstand current (3 s) | 20 / 25 / 31.5 / 40 kA |
| Peak through-fault current | 51–100 kA |
| Main-circuit pole DC resistance | 45 µΩ |
| Operating sequence | O–0.3s–CO–15s–CO |
| Closing / opening time | ≤50 ms / ≤30 ms |
| Operating temperature (U2, GOST 15150) | −25…+40 °C |
| Seismic withstand (MSK-64) | 8 points |
Need pricing and delivery terms?
Send your technical requirements — our specialists will prepare a quotation and contact you.