IPNO-DU Operative Power Cabinet

The IPNO-DU cabinet (Executive Point of Remote-Controlled Street Lighting) is a high-tech hardware and software package designed for modern energy-efficient lighting systems. It not only receives and distributes electrical power from 6(10)/0.4 kV packaged transformer substations, but also serves as an intelligent node within the Smart City infrastructure, providing comprehensive monitoring, metering and protection of municipal or industrial power networks. The implementation of such units allows reducing energy consumption, minimizing commercial losses, and shifting street lighting maintenance from the emergency/accident response approach to scheduled monitoring and preventive maintenance.
Key Features and Technical Advantages
Intelligent control
It supports three independent operating scenarios:
- Automatic: operation based on an astronomical time switch, a programmed schedule or light sensors;
- Remote: commands issued from the Control Center;
- Manual: direct control via the control panel for commissioning and maintenance works.
End-to-End analytics and integration with the Advanced Metering Infrastructure (AMI) / Automated Electricity Metering System (AEMS)
The equipment provides continuous fiscal and technical electricity metering by means of a built-in smart meter. It collects data on electricity consumption, loads and the statuses of equipment components, transmitting this information to the Control Center in real time. This enables immediate fault localization and prediction of network equipment deterioration.
Ultra-reliable switching
The power circuit is based on a vacuum contactor with a service life of up to 3 million switching cycles, which is three times higher than that of standard electromagnetic starters. This significantly reduces operating costs and the frequency of repair team call-outs.
Switching safety
The system continuously monitors outgoing feeders. If external voltage is detected on a line, the controller blocks the contactor closing command, thereby reliably preventing short-circuit failures.
Uninterrupted operation (versions with ATS)
In the configuration equipped with an automatic transfer switch (ATS), the IPNO-DU unit is connected to two independent power sources. If the voltage in the main phase drops or the phase is lost, the system transfers the lighting load to the backup power supply within a fraction of a second, thus preventing lighting outages in the affected area.
Technical specifications:
| Parameter | Value |
|---|---|
| Rated currents | 20 / 30 / 50 / 100 / 160 / 250 A |
| Voltage | 380 V, 50 Hz |
| Protection degree | IP54 |
| Operating temperature | −25…+45 °C |
| IPNO-DU dimensions | 1900×900×450 mm, 4 outgoing groups, 200 kg |
| IPNO-DU/ATS dimensions | 1900×900×600 mm, 6 outgoing groups, 300 kg |
Send your technical requirements — our specialists will prepare a quotation and contact you.